LB7-132(110,66) Outdoor oil-immersed type 132KV current transformer

LB7-132(110,66) Outdoor oil-immersed type 132KV current transformer
Product Detailed
Related Categories:Power Distribution Equipment
132kv current transformer 1, stable, reliable, a long life time 2, convenient maintenance. 3, ISO9001:2000

LB7-132(110,66) Outdoor oil-immersed type 132kv current transformer

feature

1, It is oil insulation system, the primary insulation is would from high voltage cable paper, and is placed several capacitor screen of voltage division in the primary insulation, which can improve electric field distributing and decrease the consumption of insulation material.

2, It will be immersed with transformer oil after desiccating under vacuum. It has advantage of stable and reliable performance of insulation, rich successful experience, a long life time and convenient maintenance.

3, Perfect fluidity performance of transformer oil is good for heat dissipation, it also has self recover ability for the failure of partial discharge caused by air bubble and dust.

 Technical data

Rated primary voltage

132(110,66)kv

Highest voltage for equipment

145(126,72.5)kv

Rated frequency

50 or 60 Hz

Rated current ratio

2×30-2×1000/5or 1A

Number of secondary windings

1-5

Accuracy of measuring winding

0.2, 0.2s, 0.5, 0.5s

Accuracy of production winding

5p or 10p

Rated secondary output

20-50va

Accuracy limit factor

15, 20, 25, 30

Instrument security factor

≤5 or ≤10

Partial discharge under 1.2Um/√3Kv

≤5Pc

Dielectric dissipation factor tg under 10KV-Um/3Kv

≤0.005

Power frequency withstand voltage on primary windings

230(275)kv 200(230)kv 140kv rms

Rated lightning impulse withstand voltage

550(650)kv 450(550)kv   325kv peak

Power frequency withstand voltage between primary sections

3kv rms

Power frequency withstand voltage on earth screen to earth

5kv rms

Power frequency withstand voltage on secondary windings and secondary windings to earth

3kv rms

secondary winding inter-turn withstand voltage

4.5kv peak

Mechanical strength(three direction)

2000N

LB7-132(110,66) Outdoor oil-immersed type 132KV current transformer