TYD110-0.01/0.02H Outdoor capacitor 110kV voltage transformer

TYD110-0.01/0.02H Outdoor capacitor 110kV voltage transformer
Product Detailed
Related Categories:Power Distribution Equipment
1,110kv single phase capacitor voltage transformer 2,safety and prevent the danger of explosion. 3,ISO certificate

TYD110-0.01/0.02H    Outdoor capacitor 110kV voltage transformer

Capacitor voltage transformer(CVT) is composed of a capacitor shunt device and a electromagnetic unit.

Capacitor shunt device is composed of high voltage capacitor and medium voltage capacitor, which is sited inner ceramic conduit and the conduit is filled with insulation oil.

The electromagnetic unit is composed of midway transformer reactor compensator damper and lighting arrester inside the oil tank. The terminal of second oil CVT low voltage terminals grounding terminals and protective clearance are inside the terminal box.

Oil sealing

The capacitor elements of CVT are sealed inner ceramic conduit which is processed with procedures of heating, vacuum dried and filling with de-hydraulic and air-free insulation oil and keep the vacuum then the oil volume variation out of temperature changing shall be adjusted through the expansion box outside the upper side of the ceramic conduit ,so as to keep the positive oil pressure inside stable at 0.0005-0.05/cm3

Technical data

Rated primary voltage

132(110, 66)/√3Kv

Highest voltage for equipment

145(126, 72.5)/√3Kv

Rated frequency

50 or 60 Hz

Rated voltage ratio

132(110, 66) / 0.1 /0.1kv

     √3              √3      

132(110, 66) / 0.1 /0.1/0.1kv

        √3           √3   √3    

Accuracy and output

Secondary terminal marking

1a-1n

2a-2n

da-dn

Accuracy

0.2

0.5

0.5

3p

3p

Rated output

100

250

300

150

150

150

Terminal limit output

2000VA

Accuracy voltage factor

1.2 times continuous ;1.5times 30s

Partial discharge under 1.2Um/√3Kv

≤10Pc

Dielectric dissipation factor under 10kv

tg ≤ 0.0015

Power frequency withstand voltage on primary windings

230(275)kv 200(230)kv 140kv rms

Rated lightning impulse withstand voltage

550(650)kv 450(550)kv   325kv peak

Power frequency withstand voltage on primary winding "N" terminal to earth

5kv rms

Power frequency withstand voltage between secondary windings and to earth

3kv rms

Mechanical strength(three direction)

2000N

        

TYD110-0.01/0.02H Outdoor capacitor 110kV voltage transformer