LB7-220 Outdoor oil-immersed type 220kV current transformer
LB7-220 Outdoor oil-immersed type 220kV current transformer
It is oil insulation system, the primary insulation is would from high voltage cable paper, and is placed several capacitor screen of voltage division in the primary insulation, which can improve electric field distributing and decrease the consumption of insulation material. It will be immersed with transformer oil after desiccating under vacuum. It has advantage of stable and reliable performance of insulation, rich successful experience, a long life time and convenient maintenance.
Perfect fluidity performance of transformer oil is good for heat dissipation, it also has self recover ability for the failure of partial discharge caused by air bubble and dust.
The current ratio can be changed easily by change the connection method of connecting plate on series or parallel connection.
Hermetically sealed stainless steel metallic bellows is stalled on the top, which protects the transformer oil from moisture and extend the life time, also there is a oil level gauge on the bellows for observing the changing of oil volume.
There is a multifunction oil drain valve on the base, which makes it more convenient for sampling and draining.
Technical data
Rated primary voltage | 220kv |
Highest voltage for equipment | 252kv |
Rated frequency | 50 or 60 Hz |
Rated current ratio | 2×300-2×1000/5or 1A |
Number of secondary windings | 1-8 |
Accuracy of measuring winding | 0.2, 0.2s, 0.5, 0.5s |
Accuracy of production winding | 5p or 10p |
Rated secondary output | 20-50VA |
Accuracy limit factor | 15, 20, 25, 30 |
Instrument security factor | ≤5 or 10 |
Partial discharge under 1.2Um/√3Kv | ≤5Pc |
Dielectric dissipation factor tg under 10KV-Um/3Kv | ≤0.005 |
Power frequency withstand voltage on primary windings | 395kv rms |
Rated lightning impulse withstand voltage | 950kv peak |
Power frequency withstand voltage between primary sections | 3kv rms |
Power frequency withstand voltage on earth screen to earth | 5kv rms |
Power frequency withstand voltage on secondary windings and secondary windings to earth | 3kv rms |
secondary winding inter-turn withstand voltage | 4.5kv peak |
Mechanical strength(three direction) | 2500N |